Thermodynamic Design

Thermodynamic traps work on the difference on dynamic response to velocity change in flow of compressible and incompressible fluids. It controls the discharge with a one moving part, a metal circular disc. This design is essentially a "time cycle" device and does not respond to load variations. Every time this design cycles 0.032 lbs. of steam is lost.

Pressure Ranges

  • 20-600 psig
  • 20-1000 psig
  • 20-1800 psig

Size Ranges

  • 1/2"
  • 3/4"
  • 1"
  • 1 1/2"
  • 2"

Comparison Data Sheets

PDFDownload Thermodynamic Data Sheet

Adobe Reader